|   Home   |  About Us   |  Contact Us   |   
Home                                    
AquaBox Specifications        
Applications                          
Q & A                                     
Order Online                         
About Us                              
Contact Us                            

  AquaBox Specifications

DESCRIPTION
The AquaBox was designed for dependable detection of low levels of conductive liquids. It is most commonly used under computer room floors, around pumps or inside drip pans.
   The Module is powered by a 24 VAC or 24-30 VDC. The relay outputs allow easy interface with any monitoring system. A green LED visible outside the box indicates power, while a red LED indicates an alarm. Red momentary switch is used as an alarm test. It shorts sensing wires, which generates alarm.    The tape is 1" wide with the sensing conductors enclosed in a sturdy polymer coated mesh. The cable material acts as a water wick by pulling the water into its openings. The cable material is hydrophobic so it is not absorbing the water it is detecting. This allows for faster drying time and faster return to service after a water leak.
   Multiple cables can be connected together to extend coverage area.

SENSING TAPE LENGTH
We offer tapes at length of 5', 10', 15' and 25'. They can be connected together to give flexibility to extend coverage area.

FEATURES
Sturdy aluminum enclosure
Alarm output DPDT relay (dry contact)
Power and alarm LED's
Alarm test switch
Continuous tape integrity self check
Easy troubleshooting

INSTALLATION

Remove the front panel of the device. Run wires through the back plate and make terminations. Reassemble the front panel. Plug the tape into the module and fasten the mounting screws.  Use the plastic clips to mount tape to a clean and dry surface. Contact cement provides more secure installation than double face tape. Fold the tape on itself to make sharp corners. Insulate tape from conduits and ground wires. A grounded tape may cause detector failure.

  

SPECIFICATIONS
Power Requirements: 24 VAC
or 24 to 30 VDC
Power Consumption: DC: 30 mA maximum
AC: 35 mA maximum
Alarm Output: DPDT: 1A at 24VAC/VDC
Enclosure: Extruded aluminum
Sensor Tape: 1" wide and 5, 10, 15 or 25 feet long.
Dimensions: 1.75" x 4.75" x 3"
   
WIRING
AquaBox is provided with round opening for ½” conduit or flex connector.
   Terminations are made to screw terminal
connectors shown below.
   Both outputs of alarm relay function identically.
   Contacts could be connected in parallel if load is heavier than 1A at 24V. Do not apply voltages greater than 30 to alarm outputs.
 

COVERED BY 5 YEAR WARRANTY

 Download AquaBox Data Sheet
ProDigi Controls Inc., 2605 Webster Dr. Plano, Tx 75075  •  Tel: 214-440-2644